Description:
The Transdata 30WRP552-12 watt/VAR transducer provides isolated 4–20 mA outputs for three-phase real and reactive power monitoring in electrical power systems and SCADA networks. Designed for three-phase, four-wire (WYE) circuits, it accepts a nominal 120 VAC input and a nominal 5 A input, with a measurement range of 0–10 A at 50/60 Hz and an accuracy of ±0.2% of reading. With a response time under 400 ms and an operating temperature range from -20°C to +70°C plus 0–99% non-condensing humidity, the device also offers a surge withstand capability of 5000 V (IEEE 472) and a 2000 V RMS dielectric test (1 minute). Commonly installed in electrical distribution panels, substations, energy management systems, and industrial automation facilities for replacement, retrofit, or new energy measurement installations; common replacements include NK Technologies PW Series, Veris H8036, and Moore Industries PWV transducers.